Static Var Generator

Static Var Generator

Compared with traditional SVC devices represented by TCR, Static Var Generator (SVG) has a faster adjusting speed, wide operating voltage, and greatly reduces the carrier frequency harmonics and compensaties current after adopting multiple, multi-level PWM technology. What is more, the...
Chat Now

Product Details

Compared with traditional SVC devices represented by TCR, Static Var Generator (SVG) has a faster adjusting speed, wide operating voltage, and greatly reduces the carrier frequency harmonics and compensaties current after adopting multiple, multi-level PWM technology. What is more, the components which are used  in SVG are far smaller than SVC’s, so the size of the device can be reduced.  NPV and  NSVseries of SVG represent the development direction of  dynamic reactive power compensation with such advantages.


NPV series of SVG have realized universal coverage of the power systems, and  can be widely used in different industries and conditions. According to the voltage grade used  by users, the SVG has been divided into 200 V, 400 V, 600 V and  even  higher  voltage series.  Modularization of power units makes it more compant and it  is easy to expand. Reliability of the whole machine is greatly improved  because of  the independence of each  module.


ØFeatures

ØApplication Areas

1.200V,400V,600V,750V,1140V,Rated capacity up to 10Mvar;
2.The fault module does not affect the operation of  other modules and can be replaced by elements with high reliability;
3. Modular Parallel Design. Each module unit can be used for active power compensation independently or at the same time;
4. Strong ability to control the voltage fluctuation and flicker. Damped harmonic oscillator of power system;
5. Using PWM technology which own harmonics are low;
6. Increased capacity,reduced pawer loss,purify power;
7. Fast response(less than 3ms),low power consumption,small footprints.

1. The power system which needs comprehensive compensation of reactive power and harmonics.
2. Electric Pawer industry which use a special AC voltage.
3. The power system in low power factor areas, such as factories, enterprises, etc.
4. Production enterprise using a high-power and nonlinear load.(for example, air pump etc.)
5.Remote areas with a poor condition of electricity, such as rural, mountainous area and wind farm.
6. The power system which has a demand for high quality power grid, such as hospital equipment etc.


ØProduct parameters

Access to the grid

Wire system

Three-phase

Working voltage

200V、400V、600V、750V、1140V

Working frequency

50 Hz±5%

Compensation performance

Compensation capacity

0~10M

Power factor

›0.96(Within the scope of the power compensation)

Range of reactive power adjustment

Continuous adjustment from rated capacitive reactive power to rated inductive reactive power

Harmonic

Satisfy《The power quality of public power grid harmonic》GB/T 14549-93

Overload Current Multiples

1.2

Response time

<3ms

Reliability and Life Time

A 20-year design lifetime
     Mean time between failures MTBF›75000 hours
     Mean time to restoration MTTR<5 minutes

Control system

Control chip

DSP ( digital signal processor ),programmable gate array on site(FPGA)

Reactive compensation control chip

Reactive compensation、harmonic current compensation、negative-sequence current compensation、comprehensive compensation、constant voltage compensation

Control power supply

220VAC

Intelligent communication

TCP/IP GPRS Modbus

Display

Human Machine Interaction(HMI) with real-time display function

Protection function

Over-current、short-circuit、ground protection、overvoltage、under-voltage、in-put phase failure、over-temperature、control source fail、communication failures etc.

Control link

Fiber optic isolation、electrical connection etc.

Structural feature

System structure

Integrated design,modular design and plug and play configuration

 Protection class

IP21/IP20(Special demand may be ordered)

Environmental condition

Storage,  transportation and temperature

-40~70℃

Working Relative Humidity(%)

<95%,No condensation

Operating altitude

≤2000m

Other

Electromagnetic compatibility

Conform to GB 7251-2005(GB/T 7261-2000)